A control approach to regulate formaldehyde concentrations indoors a gross anatomy laboratory via a switched fuzzy logic system

E. J. Herrera-López, N. Pitalúa-Díaz*, J. E. Pliego-Sandoval, R. Femat, L. Velazquez, N. Munguia, A. González-Angeles

*Autor correspondiente de este trabajo

Producción científica: Contribución a una revistaArtículorevisión exhaustiva

3 Citas (Scopus)

Resumen

In this paper, a switching fuzzy logic controller (SFLC) was proposed to reduce formaldehyde (FA) concentrations in a gross anatomy laboratory. At large vapor levels a hasty fuzzy logic controller (HFLC) first is activated to decrease the hazardous concentration. A switching criterion enables a second precise fuzzy logic controller (PFLC) that smoothly takes the systems output near the desired set-point. An adaptive algorithm allowed the SFLC to select the proper number of extraction systems from 3, 6, or 9 devices. The simulated performance of the fuzzy controller was satisfactorily decreasing and stabilizing the FA concentration even in the presence of parametric disturbances at set-point values of 0.37 mg/m3 and 0.29 mg/m3. However, the performance of the SFLC deteriorated as the number of dissection tables >35. The results showed that SFLC can be considered as a promising strategy to ensure indoor air quality in gross anatomy laboratories.

Idioma originalInglés
Número de artículo107492
PublicaciónBuilding and Environment
Volumen188
DOI
EstadoPublicada - 15 ene. 2021

Nota bibliográfica

Publisher Copyright:
© 2020 Elsevier Ltd

Huella

Profundice en los temas de investigación de 'A control approach to regulate formaldehyde concentrations indoors a gross anatomy laboratory via a switched fuzzy logic system'. En conjunto forman una huella única.

Citar esto