Resumen
The thermal analysis of a Room (R) coupled with a Double Glazing Window (DGW) with/without solar control film (SCF) for warm and cold climate conditions of Mexico City is presented. The right vertical surface of the room is considered partially adiabatic and with a DGW. The DGW consists of two vertical semitransparent walls: glazing-1 facing the room, and glazing-2 facing the external environment; there is a SCF attached to glazing-1 for cold climate condition, or glazing-2 for warm climate condition. During one day, the hourly simulations of the R-DGW were done in an in-house code based on the finite volume method. To carry out the thermal analysis of the R-DGW, three cases were defined: Case C1 corresponds to the R-DGW without SCF; Case C2 and C3 correspond to the R-DGW with SCF for warm and cold climate condition, respectively. For warm climate condition the use of a SCF is highly recommended, since Case 2 reduces the amount of energy gained in ≈67.7% compared to Case 1. When using the SCF on the R-DGW for cold climate condition case C3, the average temperature inside of the room is similar to case C1.
Idioma original | Inglés |
---|---|
Páginas (desde-hasta) | 237-250 |
Número de páginas | 14 |
Publicación | Renewable Energy |
Volumen | 94 |
DOI | |
Estado | Publicada - 1 ago. 2016 |
Nota bibliográfica
Publisher Copyright:© 2016 Elsevier Ltd.